ENERPOWER
  • Structure made from high strenght steel in order to ensure greater mechanical resistance
  • Galvanized structure with magnelis ®: eco-friendly with self-healing protection, in order to ensure aesthetic results of exceptional quality
  • Available in a wide range of sizes, even for use in combination
  • Dedicated functional units for each device
  • Simplified structural assembly thanks to the components’ high degree of standardization, flexibility and modularity
  • Functional unit suitable for forms of segregation up to 4b
  • Compatibility with the various types of devices produced by the market’s leading brands and manufacturers (fixed, removable, extractable)
  • Cover panels finished in standard textured RAL7035 colour, standard ETA painting cycle with epoxy polyester powder coating
  • Cable entry from above or below for multiple installation types
  • All holes threaded M6, for an easy assembly
  • ENERPOWER system subjected to the test types required by the IEC 61439-1-2 standard, with performance guaranteed by tests carried out under normal operating conditions
  • Protection rating IP30, possibility to be increased to IP31

 

The ETA suite cabinet system with ETA tested busbar system and supports is complying with 61439-1-2:

  1. Short circuit resistance testing performed at the ABB Sace laboratory of Bergamo (Italy). Relative certification nr. 175 issued by ACAE of Bergamo (Italy) based on the LOVAG reports iussed by ABB Sace.
  2. Verification of Temperature-rise limits carried out at the I.N.RI.M. laboratory of Turin (Italy) with test report nr. 14-0114-01.
  3. Short circuit testing affected by the switches, with Icc 100kA/1s, performed at the ABB Sace laboratory of Bergamo (Italy). Relative certification n. 477 issued by ACAE of Bergamo (Italy) based on the LOVAG reports issued by ABB Sace.

 

TECHNICAL FEATURES
Rated frequency 50Hz
Rated voltage Ue 400V~ o 690V~
Rated insulated voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated current Up to 4000A In
Rated short-time withstand current Icw/1s Up to 100kA
Admissible rated peak witkstand current Ipk Up to 220kA
Forms of segregation Up to 4b
Normal opertating conditions Ambient T ≤ 40°C

Pollution rating ≤ 3

Installation height ≤ 2.000mt

 

 

Download